Characteristics and Diagnosis of Inter-Turn Short Circuit Faults in Power Transformer Windings

1. Overview of Inter-Turn Short Circuit Faults

Inter-turn short circuits occur when the insulation between adjacent turns in a transformer winding fails, creating a parallel current path. This fault is one of the most critical threats to transformer reliability, accounting for ~30% of winding failures in power transformers. Common causes include:


  • Insulation Aging: Degradation of paper/oil or epoxy insulation due to thermal stress, moisture, or chemical reactions.

  • Electrical Overstress: Lightning surges, switching transients, or harmonic voltages that breach insulation withstand limits.

  • Mechanical Damage: Winding deformation from short-circuit forces or improper installation.

  • Contamination: Particles or moisture in the insulation system leading to partial discharges (PD) and breakdown.

2. Key Fault Characteristics

2.1 Electrical Characteristics

a. Increased Winding Current

  • A shorted turn acts as a low-impedance loop, drawing excessive current (Isc) proportional to the number of shorted turns. For a winding with N turns and n shorted turns:IscZturnVNnn

    • Zturn: Impedance of a single turn.

  • This causes unbalanced currents in multi-phase transformers, triggering differential protection relays.

b. Reduced Impedance

  • The fault lowers the winding’s effective inductance, reducing the transformer’s short-circuit impedance (Z%). A decrease of 3–5% in Z% may indicate winding damage.

c. Voltage Regulation Distortion

  • Shorted turns alter the turns ratio, leading to voltage mismatches between primary and secondary sides. For example, a 1% turn loss in a 10 kV winding may cause a 100 V output deviation.

2.2 Thermal Characteristics

  • Localized Overheating: Fault currents generate joule heating (I2R), raising temperatures in the shorted region. Infrared (IR) imaging may detect hotspots exceeding 100°C, compared to the normal winding temperature (≤95°C for oil-immersed transformers).

  • Oil Degradation: Overheating decomposes transformer oil, producing gases like methane (CH₄), ethylene (C₂H₄), and hydrogen (H₂). DGA (Dissolved Gas Analysis) ratios exceeding IEC 60599 codes (e.g., C₂H₄/C₂H₆ > 3) indicate thermal faults.

2.3 Mechanical Characteristics

  • Vibration Amplification: Asymmetrical magnetic forces from shorted turns induce mechanical vibrations at frequencies of 2f (twice the power frequency). Vibration sensors may detect acceleration levels >5 g (normal: <2 g).

  • Winding Deformation: Prolonged faults can cause axial or radial displacement of windings, detected via frequency response analysis (FRA) or short-circuit impedance tests.

2.4 Acoustic and PD Characteristics

  • Arcing Noise: High-energy faults produce audible hissing or buzzing sounds due to partial discharges.

  • PD Activity: Insulation breakdown creates PD pulses, measurable via HFCT (High-Frequency Current Transformer) sensors or ultrasonic detectors. PD levels >100 pC are indicative of serious defects.

3. Diagnostic Techniques

3.1 Electrical Tests

a. DC Resistance Measurement

  • Compares resistance values between phases or windings. A deviation >2% from the average indicates possible shorted turns:ΔR=RavgRtestRavg×100%

  • Example: A 10 MVA transformer’s winding resistance shifts from 0.12 Ω to 0.11 Ω, suggesting a 5–8% turn loss.

b. Turns Ratio Test

  • Measures the voltage ratio between primary and secondary windings. A sudden change in the ratio (e.g., >0.5%) signals winding deformation or shorted turns.

c. Frequency Response Analysis (FRA)

  • Applies a swept-frequency signal (10 Hz–1 MHz) to the winding and compares the impedance frequency response to a baseline. Deviations in the resonance peaks (e.g., shift >2 kHz) indicate mechanical deformation from short circuits.

3.2 On-Line Monitoring

a. DGA (Dissolved Gas Analysis)

  • Monitors gas concentrations and ratios to classify fault severity:

    • Low-Temperature Pyrolysis (<300°C): CH₄, CO dominate.

    • High-Temperature Thermal Fault (>700°C): C₂H₄, H₂ dominate.

    • IEC 60599’s Duval triangle method correlates gas ratios to fault types.

b. Partial Discharge (PD) Monitoring

  • Uses inductive sensors (HFCT) or ultrasonic probes to detect PD pulses. A PD trend showing increasing pulse magnitude (>500 pC) or repetition rate (>100 pulses/s) indicates evolving insulation damage.

c. Dynamic Load Testing

  • Applies step loads while monitoring winding temperature rise and voltage regulation. A faster-than-normal temperature increase (e.g., >5°C/h under 75% load) may indicate hidden short circuits.

3.3 Mechanical and Thermal Diagnostics

a. Vibration Analysis

  • Uses accelerometers to capture vibration signals at the tank surface. Fourier transform analysis of the signals reveals fault-related frequencies (e.g., 2f, 3f) with amplitude increases >30% compared to baseline.

b. Infrared Thermography

  • Detects temperature gradients across windings and bushings. A hotspot with a temperature delta (ΔT) >20°C relative to adjacent areas suggests a localized fault (Figure 1).

c. Winding Deformation Test (WDT)

  • Uses low-voltage impulse (LVI) or sweep-frequency impedance (SFI) methods to assess winding geometry. Changes in the impulse response waveform’s timing or amplitude indicate turn-to-turn short circuits.

4. Fault Severity Assessment and Mitigation

4.1 Severity Classification

Fault StageKey IndicatorsRisk Level
IncipientPD <100 pC, gas levels <50 ppm (CH₄), ΔR <1%Low
DevelopedPD 100–500 pC, gas ratios approaching IEC limits, ΔR 1–3%Medium
CriticalPD >500 pC, gas ratios exceeding IEC limits, ΔT >20°CHigh

4.2 Mitigation Strategies

  • Immediate Shutdown: For critical faults (e.g., smoking, explosive noises), isolate the transformer to prevent catastrophic failure.

  • Offline Testing: Perform FRA, DGA, and DC resistance tests to confirm fault location.

  • Repair or Rewinding: Replace damaged winding sections or rewind the entire winding if >10% of turns are shorted.

  • Insulation Refurbishment: Replace aged oil and paper insulation to prevent recurrence.

5. Industry Standards and Case Studies

5.1 Standards

  • IEEE Std C57.12.90: Guidelines for transformer diagnostic testing.

  • IEC 60076-5: Specification for withstand voltage tests and partial discharge measurements.

  • ASTM D3612: Method for gas analysis in transformer oils.

5.2 Case Study: 220 kV Transformer Inter-Turn Fault

Scenario: A utility transformer experienced tripping of the differential relay during a load increase.


  • Diagnostics:

    • DGA showed C₂H₄ = 280 ppm (alert limit: 150 ppm), H₂ = 500 ppm (alert limit: 150 ppm).

    • FRA revealed a 3 kHz shift in the resonance peak of the high-voltage winding.

    • DC resistance test showed a 2.5% decrease in the faulty phase’s resistance.

  • Outcome: A 5-turn short in the HV winding was found during disassembly. The winding was rewound, and the transformer returned to service with normal parameters.

6. Future Trends in Fault Diagnosis

  • AI-Driven Diagnostics: Machine learning models (e.g., convolutional neural networks) to analyze FRA and PD data for early fault detection.

  • IoT-Based Predictive Systems: Real-time integration of sensor data with cloud platforms for automated fault triaging.

  • Non-Destructive Testing (NDT) Advances: Use of terahertz imaging to visualize insulation defects without disassembly.

7. Conclusion

Inter-turn short circuit faults pose a significant risk to power transformer reliability, but timely diagnosis through a combination of electrical tests, thermal monitoring, and gas analysis can prevent catastrophic failures. By adhering to industry standards and leveraging advanced diagnostic technologies, operators can optimize maintenance strategies, extend transformer lifespan, and ensure the stability of power grids. Proactive fault management remains critical in maintaining the resilience of modern energy infrastructure.