Auto Recloser

Farady Electric strives to bring our customers the latest technology and competitive pricing and best service for pole mounted Auto circuit recloser.

Email your specs

Detail

General

Farady Electric strives to bring our customers the latest technology and competitive pricing and best service for pole mounted Auto circuit recloser.

The FAR series Auto circuit recloser can use on overhead distribution lines as well as distribution substation applications for all voltage classes 11kV up to 38kV at 50/60HZ power system. And its rated current can reach 1600A.

The FAR series Auto circuit recloser integrates the functions of control, protection,  measurement,communication,fault detection,

on-line monitoring of closing or opening.comply to IEC62271 and ANSI/IEEE C37.60 standard.


Service Condition

a) Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃.

b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .

c) Altitude above sea level: Maximum installation altitude: 2500m or more higher.

d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.

e) No frequent violent shake.


Technical Data

No.ItemUnitdata

1

Rated voltage

kV

15

 27

 38

2

Rated current

A

630

630

630

3

Rated frequency

HZ

50/60

50/60

50/60

4

Power frequency 1min Dry

kV

50

65

70

5

Lightning  impulse  withstand  voltage(peak value)alternate,

kV

110

150

180

6

Rated short circuit breaking current

kA

16/25

16/25

16/25

7

Rated short current switching current(peak value)

kA

50

50

50

8

Rated peak value withstand current

kA

50

50

50

9

4S short time withstand current

kA

20

20

20

10

Rated operating circulate

kV

O-T1-CO-T2-CO-T3-CO-T4-CO  Or Customize

11

Breaking current frequency under rated short circuit

times

30

12

Mechanism life

times

30000

13

Secondary loop 1 min power frequency withstand voltage

kV

2


Production's Characters Description

● High quality Solid Epoxy resin material 

● Fully comply with ANSI  std     

● Guarantee 30,000 times operation 

● Environment friendly , Oil / SF6 Gas free 

● Suitble for both Pole mounted or Substation available              

● Reliable and Enhanced Life Expectancy 

● Ambient temp: -40℃~80℃


0.jpg

1. ON/OFF Indicator

2. Emergency Close

3. Counter

4. Manual OFF

5. Earthing

6. Secondary Socket

7. Magnet Mechanism


Product Structure

Production's Characters Description

● High quality Vacuum Interrupter 

● Voltage sensor Integrated       

● CT Integrated

● Reliable Push rod      

● Minimized moving components 

● Maintenance free design


1.jpg


1. Rogowski coil

2. Voltage Sensor

3. Vacuum Interrupter

4. CT

5. Conductor

6. Push Rod

7. Push Reed


Controller

2.jpg

3.jpg


Description

5.jpg

Voltlogic-351 series recloser controller is medium voltage overhead line grid monitoring unit, It can combined with vacuum circuit breaker for achieve of automatic reclose, measure monitoring, fault analysis and event records. It gives us a safety power grid for cutting line fault and automatic recovery operation and power  automation.

The controller is suitable for up to 38kV outdoor switchgear using, include: vacuum circuit breakers, oil circuit breakers and gas circuit breakers.

The controller is gathering with line protection, control, measurement and monitoring of voltage and current signals integrated automation and control devices outdoors.

The controller is a automatic management unit for single way/multi ways/ring network/two power sourcing, provided with all voltage and current signals and all functions.

The controller column switch intelligent controller supports:

Wireless (GSM/GPRS/CDMA), Ethernet mode, WIFI, optical fiber, power line carrier, RS232/485, RJ45 and other forms of communication, and can access other station premises equipment (such as TTU, FTU, DTU, etc.).


Protection Functions

Protection functions

ANSI code

Name in Device

Phase overcurrent

50P

P.OC

Overload

49

Overload

Phase Time-Overcurrent

51P

P.Curve

Ground Overcurrent

50G/N

E.F

Recloser

79

Reclose

Phase overcurrent cold load pick-up

CLPU 50

Cold Load

Switch-Onto-Fault


SOTF

Undervoltage

27

Under volt

Overvoltage

50P

P.OC


Metering

● Phase current IA, IB, IC RMS, Zero Sequency Voltage Uab, Ubc, Uca,U0

● Active power, reactive power and power factor Frequency


Control and Monitoring

Circuit breaker control : 94

Latching /acknowledgement : 86 


Features

● Protection configuration is complete, and all protection functions can be switched on and off flexibly. 

● 6 channels signal input.

● 4 channels current measure. 

● 4 channels voltage measure.

● Large capacity flash memory can record at least 100 times of historical events, and no data will loss even the power is off.

● Circuits operating loop can be used both the direct or alternating current, self-adaptation open/close brake function, which can co-work with various of breakers, and the operation is simple and reliable.

● The device has complete self-inspection function to in-service monitor the working conditions of various parts of the device, ensuring the reliability of the device.


Records

● Trip logs SOE logs Alarm Logs


Communication

● RS485, RS232 port and Ethernet

● Protocols -IEC60870-5-101, IEC60870-5-104 IEC61850 or Modbus RTU,DNP3.0


HMI Software

6.jpg


Technical Data

Inputs and Outputs


Phase Current Inputs

Parameter Range
Quantity3
Rated Current In5A
Measuring Range20 x In
Instrumentation≥ 0.1xIn±1% In
Frequency50/60Hz

Thermal Withstand: 

Continuous

10 Second

1 Second

2 x In

10 x In

40 x In

Burden @ In≤0.2VA (5A Phase element)


Sensitive Earth Current Inputs

ParameterRange
Quantity1
Rated Current In1A
Measuring Range2 x In
Instrumentation≥ 0.1xIn±1% In
Frequency50/60Hz

Thermal Withstand: 

Continuous

10 Second

1 Second

2 x In

10 x In

40 x In

Burden @ In≤0.02VA (1A Earth element)


Voltage Inputs

ParameterRange
Quantity3
Nominal40 264 Vrms
Operating Range0...264 Vrms
Instrumentation≥0.8xVn±1% Vn 
Burden @ 110V0.06 VA
Overvoltage  Withstand280 Vrms


Auxiliary Supply

ParameterRange
DC Voltage

220V

 Range 165 to 265Vrms

AC Voltage

220V

 AC 50/60Hz  AC 50/60Hz ±5%

Power consumption≤100W/300W


Unit Design

ParameterRange
Indication16 Character 8 line Display  10 LED’s
User Interface11 Navigation Keys 
Weight25kg


Communication

ParameterRange
Communication PortRS485, RS232, Ethernet
ProtocolsIEC60870-5-101
IEC60870-5-104
IEC61850 MODBUS RTU


Data Storage

ParameterRange
Events1000 times
Storage time60days


Climatic Tests

Temperature --- IEC 60068-2-1/2

ParameterRange
Display range-25℃ to +60℃
Storage range-40℃ to +70℃


Section 4

User Interface

The operator interface is designed to provide a r friendly method of controlling to user, viewing menus, entering settings and retrieving data from the relay. Four buttons are provided for navigation around the menu structure.