Capacity selection and calculation methods for power transformers
Capacity selection and calculation methods for power transformers
1、 Principles of Capacity Selection
1. The capacity of the transformer should meet the needs of the electrical load in the power supply area, that is, meet the total calculated load of all electrical equipment, and avoid the transformer from operating in an overloaded state for a long time.
For a single transformer with stable load power supply, the load rate is generally around 85%, which means the transformer capacity is about 1.15 times the calculated load. For permanent power supply systems, the load rate of transformers is generally recommended to be between 60% and 70%.
When selecting the capacity of a transformer, consideration should be given to the simultaneous power of the electrical equipment, and a transformer can be selected for installation at around 1.5 times the maximum load.
During normal operation, the transformer should withstand an electrical load of approximately 75-90% of its rated capacity. If the actual load is less than 50%, the small capacity transformer should be replaced; If it exceeds the rated capacity of the transformer, the high-capacity transformer should be replaced immediately.
2、 Methods for Capacity Calculation
1. Basic formula: Transformer capacity (kVA)=√ 3 × Rated current on the low-voltage side of the transformer (A) × Rated voltage on the low-voltage side of the transformer (V)/1000. This formula is applicable for calculating the capacity of a transformer when its rated current and rated voltage on the low-voltage side are known.
2. Formula for considering power factor: Transformer capacity (P)=√ 3 × U × I × COS φ. Among them, U is the primary voltage (kV), I is the primary current (A), and COS φ is the power factor. This formula can more accurately calculate the capacity of transformers, especially when the power factor is not equal to 1.
3. Load power calculation: First, calculate the maximum power of each phase of the load (single-phase power=voltage x current), and then calculate the total power of the three phases (three-phase total power=voltage x current x √ 3 x power factor). Finally, select the appropriate transformer capacity based on the load rate of the transformer.
3、 Precautions
When selecting transformer capacity, it is advisable to choose transformers with standard capacity specifications to facilitate procurement, installation, and maintenance.
2. For substations with important users in the power supply area, it should be considered that in the event of a fault or power outage for maintenance, other transformers can meet the primary and secondary load requirements of the users.
In urban power grids, in order to ensure the reliability and flexibility of power supply, multiple transformers can be connected in parallel for power supply. At this point, it should be noted that transformers operating in parallel should meet the conditions of equal transformation ratio, the same connection group, and the same short-circuit voltage.
4. With the increase of electricity load, it may be necessary to increase capacity or expand substations. Therefore, when selecting transformer capacity, a certain margin should be reserved to meet the demand for future load growth.
Relatenews
- Capacity selection and calculation methods for power transformers 2025-04-07 02:51:59
- The main types and characteristics of power transformers 2025-03-27 02:51:58
- Method for detecting and evaluating deformation of power transformer windings 2025-03-20 02:51:59
- Energy Efficiency Grades and Environmental Protection of Power Transformers 2025-03-10 02:51:59
- Prediction of Future Development Trends and Market Prospects for Power Transformers 2025-03-07 02:52:01
- How to Purchase and Safely Use Power Transformers: A Comprehensive Guide 2025-02-27 09:00:00
- The application prospects of power transformers in the field of new energy 2025-02-26 02:51:58
- Evaluation method for lightning impulse withstand capability of power transformers 2025-02-25 02:52:11